Shenzhen Zhong Jian South Environment Co., Ltd.

We are one of the first high-tech enterprise in the industry that provides technical solutions for air pollution control and treatment.

Manufacturer from China
Verified Supplier
2 Years
Home / Products / Modular Clean Room /

Modular Cleanrooms Achieve 98% Material Reuse For Relocation Projects

Contact Now
Shenzhen Zhong Jian South Environment Co., Ltd.
Visit Website
City:shenzhen
Province/State:guangdong
Country/Region:china
Contact Person:MissSerena
Contact Now

Modular Cleanrooms Achieve 98% Material Reuse For Relocation Projects

Ask Latest Price
Video Channel
Brand Name :ZJNF
Place of Origin :China
MOQ :1
Price :negotiate
Payment Terms :tt lc PayPal credit card
Delivery Time :18days
Packaging Details :plywood/wooden package
Overall Dimension :Customized
Body Material :Cold-roll Steel /Stainless Steel
Door Material :Stainless Steel
Filter Efficiency :99.99%
Air exchange rate :100,000-grade 10-15 times/hour
Temperature :24 C–26 C in summer; 20 to 22 DEG C in win
Material :Stainless Steel,Stailess Steel SUS304/201/Q195 /galvanized Sheet,sandwich panel,fire-proof),laminated board(scratch-proof
Application :100 Lab / Laboratory Clean Room,Pharmaceutical,Chemical Lab,Electronic plant,Hospital
Type :Clean Room Booth,Modular Designs,cleanroom
Usage :Air Purification System,Pharmaceutical factory or laboratory,Dust Free Working for lcd glass oca laminating,Laborotory,clean requirement
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

I. Core Design Process

  1. Requirement Planning & Spatial Layout

    • Define cleanliness class (ISO Class 3 to Class 8) and temperature/humidity precision (±0.1°C/±1% RH)
    • Zone functional areas: personnel purification (air showers), material transfer (pass-through windows), core production zones; optimize personnel/material flows to prevent cross-contamination
    • Reserve equipment interfaces: pre-plan equipment locations, electrical conduits, and control system wiring
  2. Structural System Design

    • Framework Selection‌: Aluminum profiles (lightweight) or SUS304 stainless steel (corrosion-resistant) with electrostatic anti-dust coating
    • Enclosure System‌:
      • Walls: Powder-coated steel/stainless steel panels with sealed joints (Class 100 zones require R50mm curved corners to prevent dust accumulation)
      • Viewing windows: Double-glazed tempered glass for visibility and airtightness
    • Floor Treatment‌: Epoxy resin/PVC flooring (chemical-resistant, anti-slip); raised floor return air systems for high-cleanliness zones
  3. Aerodynamic Configuration

    Element Technical Requirements
    FFU Layout 100% ceiling coverage for Class 100 zones; Class 10,000 zones require ≥25 air changes/hour
    Filtration System HEPA+ULPA combination (efficiency ≥99.99%@0.3μm); UV sterilization for Grade A/B zones
    Pressure Control Maintain 10–15Pa gradients (highest positive pressure in core zones) with smart dampers
  4. Smart Control System

    • 10-inch touchscreen for real-time monitoring of particle count/temperature/humidity/pressure with threshold alarms
    • IoT platform for remote adjustment of HVAC/lighting/FFU speed, reducing energy consumption by 20–30% vs. traditional systems

II. Key Construction Specifications

  1. Factory Prefabrication Stage

    • Dust-free production of modular components (wall panels/FFUs/piping) with pre-installed electrical interfaces
    • Strict QC: Air-tightness testing (≤0.01% leakage rate), material corrosion resistance verification
  2. On-Site Installation Essentials

    • Foundation preparation: Floor flatness tolerance ≤2mm/2m with moisture barrier
    • Building-block assembly:
      Non-disruptive construction: No on-site cutting permitted; 500 m² basic module assembly within 48 hours
      
  3. Validation Standards

    • Dynamic testing: Continuous 72-hour viable particle monitoring (≤1 cfu/m³ for ISO Class 5 zones)
    • Airflow visualization: Smoke tests to confirm ≤0.1% dead zones
Inquiry Cart 0